Live bid tracker
20 of 24 bids received. Aria has extracted price, ICV, technical compliance and completeness for every submission as it landed.
Bids received
0/24
Compliant
0/20
Conditional
0/20
Non-compliant
0/20
Submissions · SharePoint
All bids · auto-extracted
Avg. completeness 91% AI extracted
SharePoint·ACME · Procurement / D-TX-2026-0047 / Vendor Submissions
Last sync 05 May 2026, 14:21 GST
Connected
| Vendor | Price | Lead | ICV | Tech % | Completeness | Submitted |
|---|---|---|---|---|---|---|
NP Nexara United Arab Emirates | 13.18M | 24w | 52% | 96% | 26 Apr | |
CTW Calix India | 12.41M | 26w | 38% | 91% | 12 Apr | |
AR Arctus Türkiye | 12.87M | 38w | 34% | 91% | 22 Apr | |
SE Solara South Korea | 13.61M | 24w | 41% | 95% | 19 Apr | |
LX Lumex Morocco | 12.64M | 40w | 36% | 89% | 24 Apr | |
SG Sigma Pakistan | 12.29M | 42w | 38% | 90% | 26 Apr | |
CEI Calibra India | 11.72M | 36w | 33% | 87% | 22 Apr | |
ZHV Zenith Germany | 14.12M | 22w | 39% | 97% | 15 Apr | |
ST Stratos Romania | 12.13M | 26w | 12% | 88% | 21 Apr | |
SPG Stelar Türkiye | 12.79M | 28w | 32% | 84% | 27 Apr | |
ATG Atlas Azerbaijan | 12.48M | 30w | 30% | 82% | 26 Apr | |
CE Crestline Oman | 9.79M | 28w | 18% | 78% | 25 Apr | |
VX Voltex Greece | 13.84M | 25w | — | 92% | 23 Apr | |
AEM Altus Croatia | 13.24M | 25w | 8% | 89% | 23 Apr | |
MH Meridian China | 9.41M | 30w | 22% | 76% | 13 Apr | |
VP Vertex Vietnam | 9.12M | 32w | 26% | 72% | 25 Apr | |
SHI Summit Egypt | 11.91M | 27w | 9% | 86% | 20 Apr | |
OP Orion Greece | 12.05M | 29w | 28% | 62% | 29 Apr | |
PS Praxis Lebanon | 11.78M | 28w | 24% | 65% | 28 Apr | |
AX Apex Iraq | 10.90M | 32w | 31% | 58% | 29 Apr |
Activity stream
liveSharePoint · /Vendor Submissions
- OP29 AprOrion Power EngineeringPulled from SharePoint · 30 pp · completeness 70%
- AX29 AprApex Energy EngineeringPulled from SharePoint · 30 pp · completeness 60%
- PS28 AprPraxis Switchgear Co.Pulled from SharePoint · 31 pp · completeness 64%
- SPG27 AprStelar Power GroupPulled from SharePoint · 34 pp · completeness 96%
- ATG26 AprAtlas Transformer GroupPulled from SharePoint · 33 pp · completeness 96%
- SG26 AprSigma SwitchgearPulled from SharePoint · 35 pp · completeness 100%
- NP26 AprNexara Power SystemsPulled from SharePoint · 38 pp · completeness 100%
- CE25 AprCrestline ElectricPulled from SharePoint · 34 pp · completeness 92%
Clarification Q&A
2 published- q12 · Sec. 3.821 Apr— Calix Transformer Works
Reference Sec. 3.8 — would ACME accept a Reinhausen MS III on-load tap changer in lieu of the specified UCG-equivalent, given current MS III lead-time constraints?
Published response · circulated to all 24 vendorsYes — Reinhausen MS III is acceptable provided the vendor commits to the same ±9 × 1.25% range, motor-driven, vacuum interrupter type. ACME will conduct routine FAT witness on the OLTC sequence as per IEC 60214-1. - q15 · Sec. 3.123 Apr— Meridian HV Solutions
May we propose a Dyn11 vector group as a 'design-equivalent' to the specified YNd11?
Published response · circulated to all 24 vendorsNo. The vector group is fixed at YNd11 by ACME network design (HV neutral grounded directly, LV delta). A Dyn11 alternative is not accepted under Sec. 3.1 and would be rejected at compliance review.