ACME
PROCUREMENT INTELLIGENCE
DashboardD-TX-2026-0047Phase 3 · Bidding

Live bid tracker

20 of 24 bids received. Aria has extracted price, ICV, technical compliance and completeness for every submission as it landed.

Bids received
0/24
Compliant
0/20
Conditional
0/20
Non-compliant
0/20
Submissions · SharePoint

All bids · auto-extracted

Avg. completeness 91% AI extracted
S
SharePoint·ACME · Procurement / D-TX-2026-0047 / Vendor Submissions
Last sync 05 May 2026, 14:21 GST
Connected
VendorPriceLeadICVTech %CompletenessSubmitted
NP
Nexara
United Arab Emirates
13.18M24w52%96%
100%
26 Apr
CTW
Calix
India
12.41M26w38%91%
100%
12 Apr
AR
Arctus
Türkiye
12.87M38w34%91%
100%
22 Apr
SE
Solara
South Korea
13.61M24w41%95%
100%
19 Apr
LX
Lumex
Morocco
12.64M40w36%89%
100%
24 Apr
SG
Sigma
Pakistan
12.29M42w38%90%
100%
26 Apr
CEI
Calibra
India
11.72M36w33%87%
100%
22 Apr
ZHV
Zenith
Germany
14.12M22w39%97%
100%
15 Apr
ST
Stratos
Romania
12.13M26w12%88%
96%
21 Apr
SPG
Stelar
Türkiye
12.79M28w32%84%
96%
27 Apr
ATG
Atlas
Azerbaijan
12.48M30w30%82%
96%
26 Apr
CE
Crestline
Oman
9.79M28w18%78%
92%
25 Apr
VX
Voltex
Greece
13.84M25w92%
92%
23 Apr
AEM
Altus
Croatia
13.24M25w8%89%
92%
23 Apr
MH
Meridian
China
9.41M30w22%76%
90%
13 Apr
VP
Vertex
Vietnam
9.12M32w26%72%
90%
25 Apr
SHI
Summit
Egypt
11.91M27w9%86%
88%
20 Apr
OP
Orion
Greece
12.05M29w28%62%
70%
29 Apr
PS
Praxis
Lebanon
11.78M28w24%65%
64%
28 Apr
AX
Apex
Iraq
10.90M32w31%58%
60%
29 Apr

Activity stream

live
SharePoint · /Vendor Submissions
  • OP
    Orion Power Engineering
    Pulled from SharePoint · 30 pp · completeness 70%
    29 Apr
  • AX
    Apex Energy Engineering
    Pulled from SharePoint · 30 pp · completeness 60%
    29 Apr
  • PS
    Praxis Switchgear Co.
    Pulled from SharePoint · 31 pp · completeness 64%
    28 Apr
  • SPG
    Stelar Power Group
    Pulled from SharePoint · 34 pp · completeness 96%
    27 Apr
  • ATG
    Atlas Transformer Group
    Pulled from SharePoint · 33 pp · completeness 96%
    26 Apr
  • SG
    Sigma Switchgear
    Pulled from SharePoint · 35 pp · completeness 100%
    26 Apr
  • NP
    Nexara Power Systems
    Pulled from SharePoint · 38 pp · completeness 100%
    26 Apr
  • CE
    Crestline Electric
    Pulled from SharePoint · 34 pp · completeness 92%
    25 Apr

Clarification Q&A

2 published
  • q12 · Sec. 3.821 Apr
    Calix Transformer Works

    Reference Sec. 3.8 — would ACME accept a Reinhausen MS III on-load tap changer in lieu of the specified UCG-equivalent, given current MS III lead-time constraints?

    Published response · circulated to all 24 vendorsYes — Reinhausen MS III is acceptable provided the vendor commits to the same ±9 × 1.25% range, motor-driven, vacuum interrupter type. ACME will conduct routine FAT witness on the OLTC sequence as per IEC 60214-1.
  • q15 · Sec. 3.123 Apr
    Meridian HV Solutions

    May we propose a Dyn11 vector group as a 'design-equivalent' to the specified YNd11?

    Published response · circulated to all 24 vendorsNo. The vector group is fixed at YNd11 by ACME network design (HV neutral grounded directly, LV delta). A Dyn11 alternative is not accepted under Sec. 3.1 and would be rejected at compliance review.