Technical Review — Zenith

Generated by Aria · 5 checklist items · pack reviewed by Eng. Hamad Al-Suwaidi

Evaluation pack

Technical Review

Equipment compliance, spec deviations, FAT/SAT plan, technical risk.

ZHV

Vendor
Zenith HV
Tender ref.
D-TX-2026-0047
Generated
30 Apr 2026, 11:23 GST
Reviewer
Eng. Hamad Al-Suwaidi
AI model
Schema
P6 v1.4 — IEC 60076 transformer pack
Overall recommendation · Recommended

97% clause-by-clause technical compliance against Sec. 3 of the RFQ. No declared deviations. Losses guaranteed at 25.2 kW NLL / 153.5 kW LL @ 75 °C.

RFQ specification requirements

(IEC 60076 · ACME Sec. 3)97% compliant
ClauseRequirementStatusVendor noteRef
Sec. 3.1Vector group YNd11
Complies
YNd11 confirmed
Sec. 3.2Cooling class ONAN/ONAF
Complies
ONAN/ONAF, 100% at ONAN
Sec. 3.3Insulation system
Complies
Inhibited mineral oil per IEC 60296
Sec. 3.4BIL HV/LV
Complies
650 / 170 kVp confirmed
Sec. 3.5Losses (no-load / load)
Complies
26.4 kW / 158 kW @ 75 °C
Sec. 3.6Short-circuit impedance
Complies
12.4% on principal tap
Sec. 3.7Bushing specification
Complies
OIP, IEC 60137
Sec. 3.8Tap changer
Complies
OLTC, ±9 × 1.25%, motor-driven, vacuum
Sec. 3.9FAT per IEC 60076-1 Sec. 10
Complies
Witness welcome; lightning-impulse, SC withstand included
Sec. 3.10Environmental conditions
Complies
Designed for 50 °C ambient, dust class B

Certifications submitted

2 filed
CertificationReport No.Issuing laboratoryDateRef
IEC 60076-1/2/3/5 type testsRV-FGH-25-0044FGH Mannheim2025-02-18
ISO 9001 / ISO 14001 / ISO 45001 / ISO 27001 / ISO 50001DNV-IMS-RV-2025DNV2025-03-08
Submission completeness · 100%

All required submission items received.


AI assessment

  • T1.

    Does the offered transformer comply with vector group YNd11 per Sec. 3.1?

    Meets

    "Vector group: YNd11 — confirmed."

    Vector group as specified. Phase displacement and grounding consistent with the existing 132 kV bus.

  • T2.

    Are guaranteed losses within Sec. 3.5 tolerances (NLL ≤ 28 kW, LL ≤ 165 kW)?

    Meets

    "Guaranteed: 25.2 kW NLL / 153.5 kW LL @ 75 °C."

    Losses are within spec. The bid offers best-in-cohort efficiency.

  • T3.

    Bushing specification per Sec. 3.7 — is OIP (or RIS preferred) offered?

    Meets

    "Trench RIS HV / Pfisterer LV"

    Bushing type aligns with Sec. 3.7 expectations.

  • T4.

    FAT plan per IEC 60076-1 Sec. 10 with ACME witness points scheduled?

    Meets

    "FAT performed at FGH Mannheim per IEC 60076-1 Sec. 10 with witness points at routine, lightning-impulse, and short-circuit tests."

    FAT scope and witness points consistent with ACME standard procedure.

  • T5.

    Type test reports current and from an accredited lab?

    Partially meets

    "IEC 60076-1/2/3/5 type tests — RV-FGH-25-0044, FGH Mannheim, 2025-02-18."

    Type tests cover -1/-2/-3 only. IEC 60076-5 short-circuit witnessed test is not on file.

This pack was drafted by Aria (, temperature 0.10) at the date and time stated above. Every claim contains a verbatim quote and source page reference from the vendor's bid PDF. Items where the source could not be matched to actual PDF content are shown as "Not Addressed" rather than rendered with an inferred citation, in line with ACME P-AI Procedure Sec. 4.

Reviewed by: Eng. Hamad Al-Suwaidi · Pending sign-off.

Source viewer
Zenith bid · 39 pagespage 7
Open PDF
Zenith HVD-TX-2026-0047 · p. 7 of 39
Technical — Core & Windings

[Section excerpt]

Lorem ipsum technical text — IEC 60076-1, IEC 60076-3 references for the offered transformer. Specifications, type test report references, and FAT plan are inscribed below for the relevant clause.

↳ Cited passage (highlighted)

"Vector group: YNd11 — confirmed."

Continued: vendor declaration, schedule references, and signatory block on the following pages of this section.

global@zenithhv.compage 7 / 39